The set up for short circuit test of transformer is shown in the figure. An auto transformer is used in the circuit to adjust the input voltage precisely to the rated voltage.
The ammeter, voltmeter and watt meter are connected in the circuit to measure the current, voltage and power respectively.
In this test generally, the high voltage side is connected to the AC supply and the low voltage side is short circuited with the help of thick copper wire.
Procedure for Short Circuit Test of Transformer
- Connect the circuit as shown in the figure.
- Keep the auto transformer output at its minimum voltage position and switch on the AC supply.
- Increase the applied voltage very slowly, and adjust it to get the current equal to the rated value of the winding. Do not increase the applied voltage further.
- Note down the watt meter, voltmeter and ammeter readings. Let these are Wsc, Vsc and Isc
Parameter Calculations
The short circuit test on transformer is performed at the primary and secondary rated currents. Therefore the total copper loss is the full load copper loss.
As the iron losses are supply voltage dependent and supply voltage in this test is small, the iron losses will be negligibly small.
Hence the reading (Wsc) shown by the wattmeter is almost entirely corresponding to the full load copper loss.
We know that Wsc = VscIsccos φsc
or cos φsc = Wsc / (VscIsc)
The wattmeter reading Wsc indicates the full load copper loss.
Therefore, Wsc = Copper loss = I2scR01
or R01 = Wsc / I2sc
Where R01 is the total equivalent resistance of the transformer referred to the primary.
Similarly Z01 = Vsc / Isc = (R201 + X201)1/2
or X01 = (Z201 – R201)1/2
Where X01 is the total equivalent reactance of the transformer referred to primary.
In this way parameters R01, X01, Z01 and full load copper losses can be calculated from the short circuit test on transformer.
If the transformation ratio K is known, it is possible to obtain these parameters referred to the secondary side.
Efficiency Calculation from Short Circuit Test of Transformer
Example: A 250/500V transformer gave the following test results:
- Short circuit test with low voltage winding short circuited; 20V, 12A 100W.
- Open circuit test on low voltage side; 250V, 1A, 80W.
Determine the efficiency of the transformer when the output is 10A, 500V at 0.8 p.f. lagging.
Solution: From the short circuit test (on H.V. side)
Voltmeter reading, V2sc = 20V
Ammeter reading, I2sc = 12A
Wattmeter reading, Wc = 100W
In the short circuit test of transformer, the wattmeter measures the copper losses of the transformer on short circuit secondary current(I2sc).
Output secondary current, I2 = 10A
Copper losses at this current, Pc = (I2/I2sc)2Wc = (10/12)2 x 100 = 69.44W
From open circuit test:
In the open circuit test of transformer, the wattmeter measures the iron losses occurred in the transformer.
Therefore, iron losses in the transformer (Pi) = 80W
Output power at given load = V2I2cosɸ2 = 500 x 10 x 0.8 = 4000W
Efficiency of transformer = [output/(output + Pi + Pc)] x 100
= [4000/(4000 + 80 + 69.44)] x 100 = 96.4%
Thanks for reading about “short circuit test of transformer “.
Transformer | All Posts
- Ideal Transformer
- Construction of Three Phase Transformer
- Types of Transformers
- Equivalent Resistance and Reactance of Transformer
- Equivalent Circuit of Single Phase Transformer
- Power Loss in a Transformer
- Open Circuit Test of Single Phase Transformer
- Short Circuit Test on Single Phase Transformer
- Transformer Efficiency
- Regulation of Transformer
- Autotransformer
- Instrument Transformers
- Polarity of Transformer Windings
- Significance of Vector Group of Transformer
- Buchholz Relay Construction | Working
- Why current transformer secondary should not be opened
- Dielectric Strength Test of Transformer Oil
- Transformer Moisture Removal Process
© https://www.yourelectricalguide.com/ short circuit test of transformer.